[AE] Power system stability and load flow - part 3

12 facts. Swipe through the cards.
Free PSC questions in your emailLDC, LGS, prelims and more. Tell us your exam and get practice questions free.Sign up free
  1. Fact 1 of 12

    Balancer bus: the slack bus

    The balancer bus, or slack bus, takes up the extra power. Why: losses are unknown until the solution is found. Like a KSEB substation covering any extra demand. Recall: which bus balances losses? Answer: slack bus.

  2. Fact 2 of 12

    Generator bus: the PV bus

    A PV bus has fixed real power P and fixed voltage V. Why: its generator adjusts reactive power Q to hold voltage. Like a Kerala hydro station holding steady voltage. Recall: which bus has fixed P and V? Answer: PV bus.

  3. Fact 3 of 12

    Load bus: the PQ bus

    A PQ bus has known real power P and reactive power Q. Why: it is a load, so its voltage and angle must be solved. Like a house on a KSEB meter, where demand is what you draw. Recall: which bus has known P and Q? Answer: PQ bus.

  4. Fact 4 of 12

    Fast decoupled: proposed in 1974

    Fast decoupled load flow was proposed by Stott and Alsac in 1974. Why: it is a simplified, faster version of Newton-Raphson for big grids. Exam tip: remember the year and the two names. Recall: who proposed it along with Stott? Answer: Alsac.

  5. Fact 5 of 12

    P goes with angle, Q with voltage

    Fast decoupled splits the P-theta and Q-V problems. Why: line reactance X is much larger than resistance R, so the coupling is weak. Like checking units and fixed charge separately on a KSEB bill. Recall: which pair is decoupled? Answer: P-theta and Q-V.

  6. Fact 6 of 12

    Two matrices, formed once

    Fast decoupled uses constant matrices B' and B'', built once from Ybus. Why: they are not recalculated each iteration, which saves time. Like using one monthly tariff table for every bill. Recall: how often are B' and B'' formed? Answer: once.

  7. Fact 7 of 12

    Cheaper steps, more steps

    Fast decoupled converges linearly, while Newton-Raphson converges quadratically. Why: it needs more iterations, but each one is cheaper. Like a cheap bus taking more stops than a fast taxi. Recall: which method converges quadratically? Answer: Newton-Raphson.

  8. Fact 8 of 12

    Flat start for fast decoupled

    A flat start sets every unknown voltage to 1.0 per unit and every angle to 0 degrees. Why: it gives a neutral starting guess when no load flow is known. Like a KSEB meter reset to zero before a new reading. Recall: angle at flat start? Answer: 0 degrees.

  9. Fact 9 of 12

    Weak point: high R/X lines

    Fast decoupled assumes R is much smaller than X in every line. Why: thin distribution feeders break this, so convergence can slow or fail. Like a thin, old wire heating up on a long run. Recall: which ratio must be small? Answer: R/X.

  10. Fact 10 of 12

    Counting unknowns in load flow

    Unknowns = 2n - 2 - m, where n is total buses and m is PV buses. Why: the slack bus is fixed, and PV buses have fixed voltage. Like counting fixed charges on a KSEB bill before billing units. Recall: besides slack, which buses have fixed voltage? Answer: PV buses.

  11. Fact 11 of 12

    Newton-Raphson: full Jacobian

    Newton-Raphson uses a full Jacobian that changes at each iteration. Why: it converges quadratically and is accurate for most studies. Like a KSEB linesman checking every wire on each visit. Recall: which matrix changes each iteration? Answer: Jacobian.

  12. Fact 12 of 12

    Choosing the method

    Fast decoupled suits quick, repeated studies on large transmission grids. Why: it uses less time and memory per iteration. Like a pressure cooker finishing rice faster than an open pot. Recall: which grid size suits fast decoupled? Answer: large transmission.