[AE] Per unit system, symmetrical components and faults - part 1
- Fact 1 of 12📏
Per unit: a value compared to its base
Per unit (pu) = actual value ÷ base value, so 0.8 pu means 80% of base. Like a scooter doing 40 km/h when its base is 50 km/h. Recall: what is pu? (actual ÷ base)
- Fact 2 of 12🧮
Base impedance formula
Base impedance in ohms = (base kV line-to-line)² ÷ base MVA. Used to convert any impedance into pu. Recall: what is base impedance in terms of kV and MVA?
- Fact 3 of 12🔌
Base current for three-phase systems
Base current in amperes = base kVA ÷ (√3 × base kV line-to-line). Used for KSEB 33 kV feeder calculations. Recall: which voltage goes into this formula, line or phase?
- Fact 4 of 12🔁
Transformer pu impedance stays the same
Pu impedance does not change when you move it to the other side, if base voltages follow the turns ratio. Saves recalculating through transformers. Recall: does pu impedance change across a transformer?
- Fact 5 of 12🔍
Pu values make errors easy to spot
Pu values of similar equipment often fall in a narrow range, so a wrong value stands out. Like a KSEB meter reading far too high. Recall: why do pu values help spot wrong data?
- Fact 6 of 12🔺
Fortescue's 1918 method
C. L. Fortescue published symmetrical components in 1918. He showed any unbalanced three-phase set splits into positive, negative and zero sequence sets. Recall: who introduced symmetrical components, and in which year?
- Fact 7 of 12➡️
Positive sequence: normal balanced order
Positive sequence phasors follow a-b-c order, 120° apart, like a healthy supply. Normal balanced load flow uses this sequence. Recall: which sequence is the normal balanced one?
- Fact 8 of 12⬅️
Negative sequence: reversed order
Negative sequence phasors follow a-c-b order, the reverse of normal. They appear in unbalanced faults and heat generator rotors. Recall: what phase order does negative sequence follow?
- Fact 9 of 120️⃣
Zero sequence: three equal, in-phase phasors
Zero sequence phasors are equal in magnitude and in phase. Zero sequence current needs an earth or neutral return path, and delta windings trap it. Recall: what path does zero sequence current need?
- Fact 10 of 12🔄
Operator a rotates by 120°
a = 1∠120° = −0.5 + j0.866, and a² = 1∠240°. It shifts a phasor by 120° without changing its size. Recall: by what angle does operator a rotate a phasor?
- Fact 11 of 12📐
Sequence voltage formulas
V1 = (Va + aVb + a²Vc) ÷ 3 and V2 = (Va + a²Vb + aVc) ÷ 3. V0 = (Va + Vb + Vc) ÷ 3. Recall: which formula gives zero sequence voltage?
- Fact 12 of 12🧩
Split one hard problem into three easy ones
Each sequence network is solved alone, like three simple balanced circuits. The results are then added phase by phase. Used in fault study on a 33 kV feeder. Recall: how many sequence networks are solved?