[BOTH] Transformer losses, tests, efficiency - part 1
- Fact 1 of 12๐
Iron loss stays fixed at every load
Iron loss, also called core loss, stays almost constant at every load because it depends on voltage and frequency, not current. A KSEB transformer still wastes it at midnight with no load. Recall: does iron loss change with load?
- Fact 2 of 12๐งฒ
Iron loss = hysteresis loss plus eddy current loss
Hysteresis loss comes from the core's magnetism repeatedly flipping direction. Eddy current loss comes from currents circulating inside the core. Recall: what two losses make up iron loss?
- Fact 3 of 12๐งฑ
Laminated core cuts eddy current loss
The core is built from thin, insulated steel sheets called laminations. The thin sheets block large circulating currents, so eddy current loss falls. Recall: what core design reduces eddy current loss?
- Fact 4 of 12โก
Copper loss = I^2 x R, so it changes with load
Copper loss is I^2 x R, where I is load current and R is winding resistance. Like an autorickshaw climbing a hill, heavier current heats the wire fast. Recall: does copper loss depend on current or voltage?
- Fact 5 of 12๐
At half load, copper loss is one-quarter
Copper loss goes with current squared, so at half load it is one-quarter of full-load copper loss. It is like a scooter's wiring running cool at half throttle. Recall: copper loss at half load is what fraction of full-load value?
- Fact 6 of 12๐ฏ
Maximum efficiency: copper loss equals iron loss
A transformer is most efficient when copper loss equals iron loss. Efficiency = output / (output + iron loss + copper loss). Recall: at maximum efficiency, copper loss equals what?
- Fact 7 of 12๐
OC test gives iron loss
In the open circuit (OC) test, the secondary is left open and rated voltage is applied, so the wattmeter reads iron loss because the current is small. Recall: which test gives iron loss?
- Fact 8 of 12๐
OC test is done on the low-voltage side
In the OC test, the high-voltage side is left open and rated voltage is fed to the low-voltage side, which is the convenient supply side. Recall: which side is energized in the OC test?
- Fact 9 of 12๐
SC test gives copper loss
In the short circuit (SC) test, the low-voltage side is shorted and reduced voltage is applied until full-load current flows, so the wattmeter reads full-load copper loss. Recall: which test gives copper loss?
- Fact 10 of 12๐ชซ
SC test voltage is low, so iron loss is negligible
Only a small voltage is applied in the SC test, so core flux and iron loss are tiny and the wattmeter shows mainly copper loss. Recall: why is iron loss negligible in the SC test?
- Fact 11 of 12๐
Transformer losses are measured in watts
Iron loss and copper loss are both power losses, measured in watts (W), and are read directly from the wattmeter in these tests. Recall: what is the unit of iron loss?
- Fact 12 of 12๐
At no load, copper loss is almost zero
At no load the secondary carries no current, so copper loss is almost zero and iron loss becomes the main loss. Recall: at no load, which loss is the main one?