[BOTH] Transformer losses, tests, efficiency - part 1

12 facts. Swipe through the cards.
Free PSC questions in your emailLDC, LGS, prelims and more. Tell us your exam and get practice questions free.Sign up free
  1. Fact 1 of 12

    Iron loss stays fixed at every load

    Iron loss, also called core loss, stays almost constant at every load because it depends on voltage and frequency, not current. A KSEB transformer still wastes it at midnight with no load. Recall: does iron loss change with load?

  2. Fact 2 of 12

    Iron loss = hysteresis loss plus eddy current loss

    Hysteresis loss comes from the core's magnetism repeatedly flipping direction. Eddy current loss comes from currents circulating inside the core. Recall: what two losses make up iron loss?

  3. Fact 3 of 12

    Laminated core cuts eddy current loss

    The core is built from thin, insulated steel sheets called laminations. The thin sheets block large circulating currents, so eddy current loss falls. Recall: what core design reduces eddy current loss?

  4. Fact 4 of 12

    Copper loss = I^2 x R, so it changes with load

    Copper loss is I^2 x R, where I is load current and R is winding resistance. Like an autorickshaw climbing a hill, heavier current heats the wire fast. Recall: does copper loss depend on current or voltage?

  5. Fact 5 of 12

    At half load, copper loss is one-quarter

    Copper loss goes with current squared, so at half load it is one-quarter of full-load copper loss. It is like a scooter's wiring running cool at half throttle. Recall: copper loss at half load is what fraction of full-load value?

  6. Fact 6 of 12

    Maximum efficiency: copper loss equals iron loss

    A transformer is most efficient when copper loss equals iron loss. Efficiency = output / (output + iron loss + copper loss). Recall: at maximum efficiency, copper loss equals what?

  7. Fact 7 of 12

    OC test gives iron loss

    In the open circuit (OC) test, the secondary is left open and rated voltage is applied, so the wattmeter reads iron loss because the current is small. Recall: which test gives iron loss?

  8. Fact 8 of 12

    OC test is done on the low-voltage side

    In the OC test, the high-voltage side is left open and rated voltage is fed to the low-voltage side, which is the convenient supply side. Recall: which side is energized in the OC test?

  9. Fact 9 of 12

    SC test gives copper loss

    In the short circuit (SC) test, the low-voltage side is shorted and reduced voltage is applied until full-load current flows, so the wattmeter reads full-load copper loss. Recall: which test gives copper loss?

  10. Fact 10 of 12

    SC test voltage is low, so iron loss is negligible

    Only a small voltage is applied in the SC test, so core flux and iron loss are tiny and the wattmeter shows mainly copper loss. Recall: why is iron loss negligible in the SC test?

  11. Fact 11 of 12

    Transformer losses are measured in watts

    Iron loss and copper loss are both power losses, measured in watts (W), and are read directly from the wattmeter in these tests. Recall: what is the unit of iron loss?

  12. Fact 12 of 12

    At no load, copper loss is almost zero

    At no load the secondary carries no current, so copper loss is almost zero and iron loss becomes the main loss. Recall: at no load, which loss is the main one?