[BOTH] Transmission line parameters - part 3
- Fact 1 of 12๐
GMD: the average spacing between phases
GMD (Geometric Mean Distance) is the average spacing between the three phase conductors, used because towers rarely space them equally. Formula: GMD = cube root of (D12 x D23 x D31). Recall: what does GMD stand for?
- Fact 2 of 12๐
Equal spacing makes GMD simple
If the three phases are equally spaced at D, then GMD = D. Like a bus stop midway between two points, the average is just the spacing itself. Recall: GMD for equal spacing D is what?
- Fact 3 of 12๐ต
GMR: the effective radius of a conductor
GMR (Geometric Mean Radius) is about 0.7788 times the physical radius for a solid round conductor. Why: current crowds to the surface, so the effective radius is smaller. Recall: GMR of a solid round conductor is what fraction of its radius?
- Fact 4 of 12๐งฒ
Inductance formula: GMD and GMR together
Per-phase inductance is L = 2 x 10^-7 x ln(GMD/GMR) henry per metre. Wider spacing raises inductance, and a larger GMR lowers it. Recall: which ratio sits inside the log?
- Fact 5 of 12โก
Capacitance formula uses the physical radius
Per-phase capacitance is C = 2 x pi x 8.854 x 10^-12 / ln(GMD/r) farad per metre, where r is the physical radius. Wider spacing lowers capacitance. Recall: which radius appears in this formula?
- Fact 6 of 12๐ฃ
Short line: up to about 80 km
A short line is up to about 80 km, like a 33 kV town feeder. Its shunt capacitance is neglected, so only series R and L are modelled, because the charging current is tiny. Recall: what is the short line length limit?
- Fact 7 of 12๐
Medium line: 80 km to 250 km
A medium line runs from about 80 km to 250 km. Its capacitance is lumped and modelled in a nominal pi or T circuit, because capacitance now matters but not fully. Recall: what is the medium line length range?
- Fact 8 of 12๐
Long line: above 250 km
A long line is above 250 km. Its R, L and C are spread along the length, so it needs distributed-parameter equations with hyperbolic functions. Why: small lumped models stop being accurate. Recall: which functions solve long lines?
- Fact 9 of 12๐
Bundled conductors: several wires per phase
Bundled conductors use two or more sub-conductors per phase, held apart by spacers. Why: they reduce corona loss and surface stress on high-voltage lines. Recall: what is a bundle per phase?
- Fact 10 of 12๐งต
Bundling raises GMR and cuts reactance
Splitting one conductor into a bundle raises the effective GMR, which lowers the line's reactance. Why: a bigger GMR means less inductance per phase. Recall: does bundling raise GMR or GMD?
- Fact 11 of 12๐งฎ
Two-conductor bundle formula
For two sub-conductors of radius r spaced d apart, effective GMR = square root of (0.7788 x r x d). Recall: which two quantities sit under the square root?
- Fact 12 of 12๐
GMD/GMR is unitless
GMD and GMR are both lengths in metres, so their ratio is unitless. Why: the log term needs no unit conversion in the formula. Recall: is GMD/GMR unitless or in metres?