[BOTH] Transmission line parameters - part 3

12 facts. Swipe through the cards.
Free PSC questions in your emailLDC, LGS, prelims and more. Tell us your exam and get practice questions free.Sign up free
  1. Fact 1 of 12

    GMD: the average spacing between phases

    GMD (Geometric Mean Distance) is the average spacing between the three phase conductors, used because towers rarely space them equally. Formula: GMD = cube root of (D12 x D23 x D31). Recall: what does GMD stand for?

  2. Fact 2 of 12

    Equal spacing makes GMD simple

    If the three phases are equally spaced at D, then GMD = D. Like a bus stop midway between two points, the average is just the spacing itself. Recall: GMD for equal spacing D is what?

  3. Fact 3 of 12

    GMR: the effective radius of a conductor

    GMR (Geometric Mean Radius) is about 0.7788 times the physical radius for a solid round conductor. Why: current crowds to the surface, so the effective radius is smaller. Recall: GMR of a solid round conductor is what fraction of its radius?

  4. Fact 4 of 12

    Inductance formula: GMD and GMR together

    Per-phase inductance is L = 2 x 10^-7 x ln(GMD/GMR) henry per metre. Wider spacing raises inductance, and a larger GMR lowers it. Recall: which ratio sits inside the log?

  5. Fact 5 of 12

    Capacitance formula uses the physical radius

    Per-phase capacitance is C = 2 x pi x 8.854 x 10^-12 / ln(GMD/r) farad per metre, where r is the physical radius. Wider spacing lowers capacitance. Recall: which radius appears in this formula?

  6. Fact 6 of 12

    Short line: up to about 80 km

    A short line is up to about 80 km, like a 33 kV town feeder. Its shunt capacitance is neglected, so only series R and L are modelled, because the charging current is tiny. Recall: what is the short line length limit?

  7. Fact 7 of 12

    Medium line: 80 km to 250 km

    A medium line runs from about 80 km to 250 km. Its capacitance is lumped and modelled in a nominal pi or T circuit, because capacitance now matters but not fully. Recall: what is the medium line length range?

  8. Fact 8 of 12

    Long line: above 250 km

    A long line is above 250 km. Its R, L and C are spread along the length, so it needs distributed-parameter equations with hyperbolic functions. Why: small lumped models stop being accurate. Recall: which functions solve long lines?

  9. Fact 9 of 12

    Bundled conductors: several wires per phase

    Bundled conductors use two or more sub-conductors per phase, held apart by spacers. Why: they reduce corona loss and surface stress on high-voltage lines. Recall: what is a bundle per phase?

  10. Fact 10 of 12

    Bundling raises GMR and cuts reactance

    Splitting one conductor into a bundle raises the effective GMR, which lowers the line's reactance. Why: a bigger GMR means less inductance per phase. Recall: does bundling raise GMR or GMD?

  11. Fact 11 of 12

    Two-conductor bundle formula

    For two sub-conductors of radius r spaced d apart, effective GMR = square root of (0.7788 x r x d). Recall: which two quantities sit under the square root?

  12. Fact 12 of 12

    GMD/GMR is unitless

    GMD and GMR are both lengths in metres, so their ratio is unitless. Why: the log term needs no unit conversion in the formula. Recall: is GMD/GMR unitless or in metres?