[BOTH] Insulators, string efficiency, corona - part 2

12 facts. Swipe through the cards.
Free PSC questions in your emailLDC, LGS, prelims and more. Tell us your exam and get practice questions free.Sign up free
  1. Fact 1 of 12

    Corona: air around a wire breaks down

    Corona is ionisation of the air around a conductor when the surface field crosses about 30 kV per cm, the breakdown strength of air. Wet KSEB lines in monsoon hiss for this reason; what is this air-ionisation effect called?

  2. Fact 2 of 12

    Why corona is worse in rain and fog

    Rain drops, dust and sharp burrs make the conductor surface uneven, so local field peaks are higher and corona starts sooner. A 110 kV line hisses more on a foggy night than on a dry day. Recall: what makes the surface uneven?

  3. Fact 3 of 12

    Thin wire, more corona

    The field at a conductor surface is highest where the radius is small, so thin wires start corona first. That is why EHV lines use bundled conductors. Recall: which conductor arrangement reduces corona?

  4. Fact 4 of 12

    Critical disruptive voltage: the starting point

    Critical disruptive voltage (Vd) is the minimum line voltage at which corona starts. Below it there is almost no corona loss; above it, loss rises fast. Recall: what is the minimum voltage for corona called?

  5. Fact 5 of 12

    Peek's formula for critical voltage

    Vd = 21.1 x m0 x delta x r x ln(D/r) kV rms per phase, with r and D in cm, m0 the surface factor and delta the air density factor. Recall: whose empirical formula is this?

  6. Fact 6 of 12

    Surface factor m0: smooth vs rough

    The surface factor m0 is 1 for a smooth polished conductor and less than 1 for stranded or rough ones. A rougher surface means corona starts at a lower voltage. Recall: what is m0 for a smooth conductor?

  7. Fact 7 of 12

    Air density factor delta: height matters

    Delta = 3.92 b / (273 + t), with b in cm of mercury and t in degree Celsius. Thinner air at high altitude lowers the critical voltage. Recall: what does delta measure?

  8. Fact 8 of 12

    Wider spacing raises critical voltage

    Vd depends on ln(D/r), so a wider conductor spacing D raises the critical disruptive voltage. Towers are spaced wider to reduce corona. Recall: does wider spacing raise or lower Vd?

  9. Fact 9 of 12

    Corona loss: why it wastes power

    Corona loss is energy wasted in ionising air, and it rises sharply once voltage exceeds Vd. It also grows with frequency, so KSEB engineers must count it in line design. Recall: what is the wasted energy called?

  10. Fact 10 of 12

    Corona damps lightning surges

    Corona flattens steep lightning and switching surges, much like a scooter's shock absorber smooths a pothole, protecting insulators and equipment. Recall: what does corona reduce on a surge?

  11. Fact 11 of 12

    Corona causes radio and TV noise

    Each corona discharge is a tiny spark, so it creates radio and TV interference and an audible hiss near lines. Recall: what does corona cause in radio reception?

  12. Fact 12 of 12

    Corona makes ozone that attacks insulation

    Corona produces ozone and oxides of nitrogen that slowly attack insulation and conductor surfaces. Ionised oxygen forms the ozone. Recall: which gas from corona damages insulators?