Do you know?
[AE] Per unit system, symmetrical components and faults - part 2
- Fact 1 of 12๐ณ
Most common fault: line-to-ground (LG)
One phase wire touches earth. This is the most common fault on lines. Why: a branch or kite touches one wire. Kerala example: a monsoon branch falls on one line near a KSEB pole. Recall: Most common fault? Answer: LG.
- Fact 2 of 12โก
LL fault: two wires touch, no earth
Two phase wires short together, and earth is not involved. Why: no earth path, so zero-sequence current is absent. Kerala example: two lines swing together in a storm and flash. Recall: Two phases short, no earth? Answer: LL fault.
- Fact 3 of 12๐
LLG fault: two wires touch and reach earth
Two phases short together, and earth is also involved. Why: earth gives a return path, so zero-sequence current flows. Kerala example: a wet coconut branch touches two lines near a house. Recall: Two phases plus earth? Answer: LLG fault.
- Fact 4 of 12๐ฅ
LLL fault: all three wires short together
All three phases short together. Why: the fault is balanced, so all three phases carry equal current. Kerala example: like an autorickshaw losing all lights at once. Recall: All three phases short? Answer: LLL fault.
- Fact 5 of 12๐ฏ
LLL is the rarest fault type
LLL is the least common fault on power lines. Why: all three phases must short together, which is less likely. Kerala example: like three scooters crashing at the same moment, rare on any road. Recall: Least common fault? Answer: LLL.
- Fact 6 of 12๐ฅ
LLL is usually the most severe fault
LLL usually gives the largest fault current. Why: all three phases carry heavy current together, with no sharing. Kerala example: like a pressure cooker valve blowing, a sudden huge release. Recall: Most severe fault? Answer: LLL.
- Fact 7 of 12๐งฎ
LG fault current formula
Ia = 3 x Ea / (Z1 + Z2 + Z0). Why: for LG, the positive, negative and zero networks are in series. Exam word: Z0 is the zero-sequence impedance. Recall: For LG, how many sequence networks are in series? Answer: three.
- Fact 8 of 12๐งฎ
LLG fault current formula
Ia1 = Ea / (Z1 + (Z2 x Z0) / (Z2 + Z0)). Why: Z2 and Z0 are in parallel for an LLG fault. Recall: In LLG, Z2 and Z0 are connected how? Answer: parallel.
- Fact 9 of 12๐งฎ
LL fault current formula
Ia1 = Ea / (Z1 + Z2), and fault current = sqrt3 x Ia1. Why: there is no zero-sequence network, so only Z1 and Z2 are in series. Recall: LL fault current in terms of Ia1? Answer: sqrt3 x Ia1.
- Fact 10 of 12๐งฎ
LLL fault current formula
Ia1 = Ea / Z1, and no Z2 or Z0 is needed. Why: the balanced fault uses only the positive-sequence network. Recall: Which sequence network does LLL need? Answer: positive only.
- Fact 11 of 12โ๏ธ
LL current is about 0.87 times LLL
With equal Z1 and Z2 and zero fault resistance, LL current is sqrt3/2 times LLL, about 0.87. Why: only two phases are shorted, so less current flows. Kerala example: a bus with two faulty wires draws less than one with three. Recall: Ratio of LL to LLL current? Answer: sqrt3/2.
- Fact 12 of 12๐
LG fault: sequence currents are equal
In an LG fault, Ia1, Ia2 and Ia0 are equal in size. Why: the three sequence networks are in series, so the same current flows through each. Kerala example: like one queue of autos moving through a single road. Recall: In LG, sequence currents are? Answer: equal.