[SE] Line performance: efficiency and regulation - part 1
- Fact 1 of 12๐
Short line: under about 80 km
A transmission line up to about 80 km is a short line. Why: its shunt capacitance is ignored, so only series R and X matter. Recall: What is the short line length limit? Answer: about 80 km.
- Fact 2 of 12๐
Short line uses series impedance only
Short line model: series impedance Z = R + jX only. Why: charging current is tiny over a short distance, so it is neglected. Recall: What two parts make up Z? Answer: R and X.
- Fact 3 of 12๐
Voltage regulation: how steady the voltage stays
Regulation = (no-load receiving voltage - full-load receiving voltage) / full-load receiving voltage x 100%. Why: it shows voltage steadiness. Recall: Divide by which voltage? Answer: full-load receiving voltage.
- Fact 4 of 12๐
Lagging load increases the voltage drop
For a short line at lagging power factor, drop is approx I R cos phi + I X sin phi. Why: reactance adds to the drop when current lags. Recall: Which term adds the reactance drop? Answer: I X sin phi.
- Fact 5 of 12๐
Leading power factor can cut regulation
A leading power factor, such as from a capacitor bank, can make regulation zero or negative. Why: capacitive current raises the receiving-end voltage. Recall: Which power factor can give negative regulation? Answer: leading.
- Fact 6 of 12โก
Line efficiency: output divided by input
Transmission efficiency = receiving-end power / sending-end power x 100%. Why: the gap between input and output is lost as heat in the conductor. Recall: Which power goes on top? Answer: receiving-end power.
- Fact 7 of 12๐ฅ
Line loss is I squared R
Power loss in a line = I^2 x R, with I in amperes and R in ohms. Why: loss rises with the square of the current. Recall: Does loss depend on current squared or current? Answer: squared.
- Fact 8 of 12๐
Double the voltage, quarter the loss
For the same power and resistance, doubling line voltage halves the current and cuts I^2 R loss to one quarter. Why: loss depends on current squared. Recall: Loss at double voltage is what fraction? Answer: one quarter.
- Fact 9 of 12๐ฏ
Lower resistance helps efficiency and regulation
Lower line resistance reduces both power loss and voltage drop. Why: both depend on the current flowing through R. Recall: Which conductor property should be lowered? Answer: resistance.
- Fact 10 of 12๐
Ferranti effect: receiving-end voltage rises
On a long, lightly loaded line, receiving-end voltage can be higher than sending-end voltage. Why: line capacitance draws leading charging current. Recall: Which effect raises receiving-end voltage at light load? Answer: Ferranti effect.
- Fact 11 of 12๐งโ๐ฌ
Ferranti effect is named after a person
The Ferranti effect is named after Sebastian Ziani de Ferranti, a British engineer. Why: the rise is caused by line capacitance, not by load. Recall: Who is the Ferranti effect named after? Answer: Sebastian Ziani de Ferranti.
- Fact 12 of 12๐ฃ๏ธ
Ferranti effect mainly on long lines
Short lines ignore capacitance, so they show almost no Ferranti rise. Why: charging current grows with line length. Recall: Ferranti effect is seen mainly in which line length? Answer: long lines.