[SE] Single phase and three phase power - part 1
- Fact 1 of 12馃殞
Real power: the work that gets done
Real power P does the actual work, like turning a bus fan motor. Its unit is the watt (W) or kilowatt (kW). Exam word: active power. Recall: what is the unit of real power? Watt or kW.
- Fact 2 of 12馃搻
Single phase real power formula
For single phase, P = V x I x cos phi, where V is volts, I is amps and cos phi is power factor. Recall: in P = V x I x cos phi, what is cos phi called? Power factor.
- Fact 3 of 12馃浐
Power factor: how much power is useful
Power factor, cos phi, is the fraction of supply power that does useful work. An autorickshaw motor with a poor power factor draws more current than its work needs. Recall: what does cos phi tell you? Useful fraction of power.
- Fact 4 of 12馃攱
Apparent power: the total power drawn
Apparent power S is the total power the supply delivers, found by S = V x I. Its unit is volt-ampere (VA) or kilovolt-ampere (kVA). Recall: what is the unit of apparent power? kVA.
- Fact 5 of 12馃攧
Reactive power: power that goes back and forth
Reactive power Q = V x I x sin phi is power that swings between supply and magnetic fields and does no useful work. Its unit is kVAR. Recall: what is the unit of reactive power? kVAR.
- Fact 6 of 12馃搹
Power triangle: P, Q and S
Real power P, reactive power Q and apparent power S form a right-angled triangle, with S as the hypotenuse. So S^2 = P^2 + Q^2. Recall: which side of the power triangle is apparent power? Hypotenuse.
- Fact 7 of 12馃彮
Why transformers are rated in kVA
Transformers are rated in kVA, not kW, because their heating losses depend on total current, not on power factor. A KSEB transformer must be sized for the full apparent load. Recall: what unit is a transformer rated in? kVA.
- Fact 8 of 12鈿欙笍
Three phase real power formula
For three phase, P = sqrt(3) x VL x IL x cos phi, where VL is line voltage and IL is line current. The square root of 3 is about 1.732. Recall: what factor separates three phase from single phase here? Square root of 3.
- Fact 9 of 12馃攲
Three phase apparent power in kVA
Three phase apparent power is S = sqrt(3) x VL x IL, and dividing the result by 1000 gives kVA. This is the figure used to size three phase equipment. Recall: divide volt-amps by what to get kVA? 1000.
- Fact 10 of 12馃М
Three phase reactive power formula
For three phase, reactive power is Q = sqrt(3) x VL x IL x sin phi, measured in kVAR. It uses sin phi where real power uses cos phi. Recall: which trigonometric term gives reactive power? Sin phi.
- Fact 11 of 12馃嵅
Low power factor means extra current
For the same real power P, a lower cos phi needs more current, since I = P / (V x cos phi). This is why a poor power factor makes wires and cookers work harder. Recall: what happens to current when cos phi falls? It rises.
- Fact 12 of 12馃浀
Why kVA is always at least kW
Apparent power in kVA equals real power in kW divided by cos phi, so kVA is never smaller than kW. A scooter-sized motor with cos phi of 0.8 needs about 25 percent more kVA. Recall: which is bigger, kVA or kW? kVA.