[BOTH] Autotransformer and instrument transformers - part 2

12 facts. Swipe through the cards.
Free PSC questions in your emailLDC, LGS, prelims and more. Tell us your exam and get practice questions free.Sign up free
  1. Fact 1 of 12

    CT secondary: 1 A or 5 A

    The CT secondary is rated 1 A or 5 A. That small current goes to meters and relays, even when the line carries hundreds of amps. Recall: standard CT secondary rating? Answer: 1 A or 5 A.

  2. Fact 2 of 12

    PT secondary: 110 V

    The PT secondary is rated 110 V. An 11 kV line is stepped down to 110 V, a ratio of 100:1, so meters can be read safely. Recall: standard PT secondary voltage? Answer: 110 V.

  3. Fact 3 of 12

    CT is connected in series

    A CT is connected in series with the line, so the full load current passes through its primary. Kerala example: the CT on a pump-house feeder carries the motor's full current. Recall: CT connected in series or parallel? Answer: series.

  4. Fact 4 of 12

    PT is connected in parallel

    A PT is connected in parallel across the line, like a bulb across a supply. It sees full line voltage. Recall: PT connected in series or parallel? Answer: parallel.

  5. Fact 5 of 12

    Never open a CT secondary

    Never open-circuit a CT secondary while the line is live. The core saturates and a dangerously high voltage can appear across the open terminals. Recall: open CT secondary causes what? Answer: high voltage.

  6. Fact 6 of 12

    Never short a PT secondary

    Never short-circuit a PT secondary. The short draws heavy current, so the fuse blows or the PT is damaged. Recall: shorted PT secondary blows what? Answer: fuse.

  7. Fact 7 of 12

    CT ratio: primary to secondary current

    A 100/5 A CT gives 5 A on the secondary when 100 A flows on the line. Exam term: current ratio. Recall: 100/5 A CT, 100 A line gives secondary what? Answer: 5 A.

  8. Fact 8 of 12

    Why use instrument transformers?

    Meters and relays are built for small currents and low voltages. CT and PT bring the line down safely to 1 or 5 A and 110 V. Recall: main reason for CT and PT? Answer: safe scaling.

  9. Fact 9 of 12

    CT and PT isolate the meter

    The secondary circuit is electrically isolated from the high-voltage line. Kerala example: a technician reading a panel meter is shielded from the 11 kV line. Recall: what does isolation protect? Answer: the meter circuit.

  10. Fact 10 of 12

    Burden is the secondary load

    Burden is the load connected to a CT or PT secondary, measured in VA. Too many meters on one secondary reduces accuracy. Recall: unit of burden? Answer: VA.

  11. Fact 11 of 12

    Remember: CT for current, PT for voltage

    CT: C for current, connected in series. PT: P for potential, which means voltage, connected in parallel. Recall: which one is in parallel? Answer: PT.

  12. Fact 12 of 12

    Earth the secondary for safety

    One terminal of the CT and PT secondary is earthed for safety. Kerala example: panel earthing at KSEB substations protects staff if insulation fails. Recall: which secondary is earthed? Answer: CT and PT.