[AE] Transformer types and three phase transformers - part 2
- Fact 1 of 12🕐
Vector group: the clock number
Each clock hour is 30° of phase shift between HV and LV. Dyn11 means 11 × 30° = 330°, so the LV side sits 30° off the HV side. Recall: Degrees per clock hour? 30°
- Fact 2 of 12🔠
Capital letters mean HV, small letters mean LV
Capital letters (D, Y, Z) mark the HV winding; small letters (d, y, z) mark the LV winding. Kerala example: the 11 kV side on a KSEB pole is HV. Recall: Which letter case marks HV? Capital letters
- Fact 3 of 12🔺
Delta has no neutral, star has one
Delta (D) is a triangle winding with no neutral point. Star (Y) has a neutral, which lets earth fault current flow. Kerala example: the star side gives your 230 V supply and neutral. Recall: Which winding has a neutral? Star (Y)
- Fact 4 of 12🌀
Dyn11: the usual distribution vector group
Dyn11 is widely used for LV distribution. The HV delta traps third harmonics, and the LV star with neutral gives 415 V line and 230 V phase. Recall: Common distribution group? Dyn11
- Fact 5 of 12⚡
Delta gives a path for third harmonics
Delta lets third harmonic (triple-n) currents circulate, keeping the voltage waveform sinusoidal. Why: a star-star unit without delta distorts the waveform. Recall: Which winding gives the third harmonic path? Delta
- Fact 6 of 12🔁
Yy0 has zero phase shift
In Yy0, HV and LV line voltages are in phase, so the shift is zero degrees. Why: with no delta, unbalanced loads and harmonics need care, so a delta tertiary is often added. Recall: Phase shift in Yy0? Zero degrees
- Fact 7 of 12⚖️
Parallel condition 1: same voltage ratio
Parallel transformers must have the same turns ratio. Why: unequal ratios make circulating current flow even at no load. Kerala example: like linking two autorickshaw batteries of different voltage. Recall: Which condition causes no-load circulating current? Voltage ratio
- Fact 8 of 12🔄
Parallel condition 2: same polarity and phase sequence
Terminals must be connected with the same polarity and phase sequence. Why: a wrong joint creates a short circuit between the units. Kerala example: like wiring a scooter battery with reversed poles. Recall: Wrong polarity causes what? Short circuit
- Fact 9 of 12🔗
Parallel condition 3: same vector group
Parallel transformers must have the same clock number, so their phase shifts match. Why: a mismatch gives a huge circulating current. Dyn11 and Yyn0 must not be paralleled. Recall: Can Dyn11 and Yyn0 run in parallel? No
- Fact 10 of 12📉
Parallel condition 4: equal percentage impedance
Load is shared in proportion to kVA rating only when percentage impedances are equal. Why: a lower impedance unit takes extra current and may overload. Recall: Equal % impedance shares load in proportion to what? kVA rating
- Fact 11 of 12〰️
Also needed: same frequency
Both transformers must run at the same frequency, which is 50 Hz in India. Why: a frequency mismatch makes the units fight each other. Kerala example: all KSEB feeders run at the same 50 Hz supply. Recall: Supply frequency in India? 50 Hz
- Fact 12 of 12🧮
Percentage impedance formula
%Z = (Z × I rated ÷ V rated) × 100. Why: it compares the voltage drop at full load with the rated voltage. Exam tip: a small %Z means a higher short-circuit current. Recall: What does %Z compare? Voltage drop vs rated voltage