    Vector group: the clock number

    Each clock hour is 30° of phase shift between HV and LV. Dyn11 means 11 × 30° = 330°, so the LV side sits 30° off the HV side. Recall: Degrees per clock hour? 30°

  2. Fact 2 of 12

    Capital letters mean HV, small letters mean LV

    Capital letters (D, Y, Z) mark the HV winding; small letters (d, y, z) mark the LV winding. Kerala example: the 11 kV side on a KSEB pole is HV. Recall: Which letter case marks HV? Capital letters

  3. Fact 3 of 12

    Delta has no neutral, star has one

    Delta (D) is a triangle winding with no neutral point. Star (Y) has a neutral, which lets earth fault current flow. Kerala example: the star side gives your 230 V supply and neutral. Recall: Which winding has a neutral? Star (Y)

  4. Fact 4 of 12

    Dyn11: the usual distribution vector group

    Dyn11 is widely used for LV distribution. The HV delta traps third harmonics, and the LV star with neutral gives 415 V line and 230 V phase. Recall: Common distribution group? Dyn11

  5. Fact 5 of 12

    Delta gives a path for third harmonics

    Delta lets third harmonic (triple-n) currents circulate, keeping the voltage waveform sinusoidal. Why: a star-star unit without delta distorts the waveform. Recall: Which winding gives the third harmonic path? Delta

  6. Fact 6 of 12

    Yy0 has zero phase shift

    In Yy0, HV and LV line voltages are in phase, so the shift is zero degrees. Why: with no delta, unbalanced loads and harmonics need care, so a delta tertiary is often added. Recall: Phase shift in Yy0? Zero degrees

  7. Fact 7 of 12

    Parallel condition 1: same voltage ratio

    Parallel transformers must have the same turns ratio. Why: unequal ratios make circulating current flow even at no load. Kerala example: like linking two autorickshaw batteries of different voltage. Recall: Which condition causes no-load circulating current? Voltage ratio

  8. Fact 8 of 12

    Parallel condition 2: same polarity and phase sequence

    Terminals must be connected with the same polarity and phase sequence. Why: a wrong joint creates a short circuit between the units. Kerala example: like wiring a scooter battery with reversed poles. Recall: Wrong polarity causes what? Short circuit

  9. Fact 9 of 12

    Parallel condition 3: same vector group

    Parallel transformers must have the same clock number, so their phase shifts match. Why: a mismatch gives a huge circulating current. Dyn11 and Yyn0 must not be paralleled. Recall: Can Dyn11 and Yyn0 run in parallel? No

  10. Fact 10 of 12

    Parallel condition 4: equal percentage impedance

    Load is shared in proportion to kVA rating only when percentage impedances are equal. Why: a lower impedance unit takes extra current and may overload. Recall: Equal % impedance shares load in proportion to what? kVA rating

  11. Fact 11 of 12

    Also needed: same frequency

    Both transformers must run at the same frequency, which is 50 Hz in India. Why: a frequency mismatch makes the units fight each other. Kerala example: all KSEB feeders run at the same 50 Hz supply. Recall: Supply frequency in India? 50 Hz

  12. Fact 12 of 12

    Percentage impedance formula

    %Z = (Z × I rated ÷ V rated) × 100. Why: it compares the voltage drop at full load with the rated voltage. Exam tip: a small %Z means a higher short-circuit current. Recall: What does %Z compare? Voltage drop vs rated voltage