[BOTH] Transformer losses, tests, efficiency - part 2
- Fact 1 of 12馃搱
Transformer peak efficiency rule
Efficiency is highest when copper loss equals iron loss. Like a scooter at its best speed, not its fastest. Recall: Max efficiency when Cu loss = ? (Iron loss)
- Fact 2 of 12馃М
Load fraction for max efficiency
Max efficiency comes at x = sqrt(Pi / Pcu) of full load, where Pi is iron loss and Pcu is full-load copper loss. Recall: Pi = 400 W, Pcu = 1600 W, so x = ? (0.5)
- Fact 3 of 12馃Р
Iron loss stays steady
Iron loss, also called core loss, is almost the same at every load. It comes from hysteresis and eddy currents in the core. Recall: Does iron loss change with load? (No)
- Fact 4 of 12馃攲
Copper loss grows fast
Copper loss equals I squared R, so it varies with the square of load current. Like an overloaded bus engine heating up quickly. Recall: Copper loss varies as I to the power ? (Two)
- Fact 5 of 12鈴憋笍
All-day efficiency meaning
All-day efficiency = kWh output / kWh input over 24 hours. It shows real performance across light and heavy loads, like a KSEB meter reading over a day. Recall: All-day efficiency covers which period? (24 hours)
- Fact 6 of 12馃寵
Why distribution transformers lag
Distribution transformers often have low all-day efficiency. Iron loss runs 24 hours, but night load is light, like a pressure cooker left on low. Recall: Which loss runs all day? (Iron loss)
- Fact 7 of 12馃攱
Voltage regulation defined
Voltage regulation = (no-load V2 minus full-load V2) / full-load V2 x 100 percent. It shows how much output voltage drops, like house lights dimming when a heavy load starts. Recall: Regulation compares which two voltages? (No-load and full-load)
- Fact 8 of 12馃搲
Regulation for lagging load
For lagging power factor, approx regulation = (I R cos phi + I X sin phi) / V x 100 percent. Both resistance and reactance cause the drop. Recall: Which power factor uses plus signs? (Lagging)
- Fact 9 of 12馃攧
Leading power factor can cut regulation
With leading power factor, voltage regulation can be negative. Output voltage rises above no-load voltage, like a capacitor bank on a feeder. Recall: Leading load gives positive or negative regulation? (Negative)
- Fact 10 of 12馃З
Equivalent circuit referred to primary
All values are moved to one side, the primary. R01 = R1 + R2 prime and X01 = X1 + X2 prime. It makes one simple circuit for calculation. Recall: Which side are values referred to? (Primary)
- Fact 11 of 12馃攳
Two tests, two losses
Open circuit test gives iron loss. Short circuit test gives full-load copper loss. Each test isolates one loss, like checking a scooter's engine and brakes separately. Recall: Which test gives copper loss? (Short circuit)
- Fact 12 of 12馃Р
No-load branch of equivalent circuit
The no-load branch has core-loss resistance Rc and magnetising reactance Xm in parallel. They model iron loss and magnetising current, like the small base draw on a KSEB meter. Recall: Which element models core loss? (Rc)