[SE] Power factor and its improvement - part 2
- Fact 1 of 12๐
Synchronous condenser: a motor with no load
A synchronous motor run with no load is a synchronous condenser. Its job is to supply reactive power, not mechanical work. Recall: what does it supply? Answer: reactive power.
- Fact 2 of 12โก
Over-excited: it supplies leading kVAR
Over-excited, it draws leading current and supplies kVAR to the grid. Lagging loads like pumps and motors need this push. Recall: over-excited, does it draw leading or lagging current? Answer: leading.
- Fact 3 of 12๐
Under-excited: it absorbs kVAR
Under-excited, it draws lagging current and absorbs kVAR from the line. This helps control voltage when the load is light. Recall: which excitation absorbs kVAR? Answer: under-excited.
- Fact 4 of 12๐ญ
Why substations use synchronous condensers
They sit at substations and correct the lagging power factor of big loads. Field current controls them smoothly, unlike fixed capacitor banks. Recall: what controls its output? Answer: field current.
- Fact 5 of 12๐ ๏ธ
Phase advancer: built for induction motors
A phase advancer improves the power factor of a slip-ring induction motor. It feeds leading current into the rotor circuit. Recall: which motor type does it suit? Answer: slip-ring induction motor.
- Fact 6 of 12๐งฒ
How a phase advancer works
A small exciter, driven by the motor, feeds current to the rotor through slip rings. The stator then draws less lagging current from the supply. Recall: what carries the current to the rotor? Answer: slip rings.
- Fact 7 of 12๐ง
Phase advancer at a pump house
A large slip-ring motor running a water pump can use a phase advancer. It lifts the power factor at the motor itself, without a separate capacitor bank. Recall: where is the advancer fitted? Answer: on the motor.
- Fact 8 of 12๐
Phase advancer vs capacitor bank
A capacitor bank gives fixed kVAR. A phase advancer gives adjustable leading kVAR right at the motor. Recall: which device gives adjustable kVAR? Answer: phase advancer.
- Fact 9 of 12๐งฎ
Formula for kVAR needed
kVAR = kW x (tan phi1 - tan phi2). Phi1 is the old power factor angle and phi2 is the target angle. Recall: what is phi1? Answer: old power factor angle.
- Fact 10 of 12๐
Worked example: 100 kW load
Power factor 0.7 lag is raised to 0.95 lag. tan phi1 = 1.020 and tan phi2 = 0.329, a difference of 0.691. So kVAR = 100 x 0.691, about 69 kVAR. Recall: how much kVAR is needed? Answer: about 69 kVAR.
- Fact 11 of 12๐ข
Worked example: kVA at 0.7 power factor
kVA = kW / power factor. A 100 kW load at 0.7 power factor needs about 142.9 kVA. Recall: what is the kVA formula? Answer: kW divided by power factor.
- Fact 12 of 12๐
kVA after power factor correction
After correction the same 100 kW load runs at 0.95 power factor. So kVA = 100 / 0.95, about 105.3 kVA. Recall: what is the new kVA? Answer: about 105 kVA.