Do you know?
[SE] Induction motor starters and single phase motors - part 1
- Fact 1 of 12โก
DOL starter: full voltage at once
Direct-on-line (DOL) starting connects the motor straight to supply. Starting current is about 5 to 7 times full-load current, so lights dim, like when a water pump starts at a Kerala home. Recall: which starter applies full voltage at once? Answer: DOL.
- Fact 2 of 12๐
DOL: simplest and cheapest starter
DOL needs only a contactor, overload relay and fuses, so it is simple and cheap. Its surge current is large, so it suits small motors only. Recall: which starter is simplest? Answer: DOL.
- Fact 3 of 12โญ
Star-delta: starts in star
In star-delta starting, the motor windings are connected in star during start. Each winding then gets line voltage divided by โ3. Recall: which connection is used during start? Answer: star.
- Fact 4 of 12๐
Star-delta cuts starting current to one-third
Starting current and starting torque both fall to one-third of DOL values. Formula: I_star = I_DOL / 3. Useful for a 415 V motor at a Kerala rice mill. Recall: star-delta cuts current to what fraction? Answer: one-third.
- Fact 5 of 12โฑ๏ธ
Star-delta changeover is timed
A timer relay switches the motor from star to delta after it speeds up. The motor must have all six terminals brought out and be delta-rated for line voltage. Recall: which relay times the changeover? Answer: timer relay.
- Fact 6 of 12๐๏ธ
Star-delta fails under heavy start load
Star-delta gives low starting torque, so a heavily loaded motor may not start. A loaded crusher is a bad match for it. Recall: why can star-delta fail with heavy loads? Answer: low starting torque.
- Fact 7 of 12๐๏ธ
Autotransformer starter uses taps
An autotransformer starter reduces motor voltage using taps, commonly 50, 65 or 80 percent. It reduces the current drawn from supply during start. Recall: which starter uses taps? Answer: autotransformer.
- Fact 8 of 12๐งฎ
Autotransformer: supply current falls by k squared
If the tap ratio is k, supply current falls to k squared times DOL current. Formula: I_supply = kยฒ ร I_DOL, so a 50% tap gives one-quarter. Recall: at a 50% tap, supply current is what fraction of DOL? Answer: one-quarter.
- Fact 9 of 12๐ช
Autotransformer suits large motors
An autotransformer starter can give more starting torque than star-delta, because the tap can be chosen to suit the load. It is costly and bulky, so it is used for large motors. Recall: which starter suits large motors with heavy starting load? Answer: autotransformer.
- Fact 10 of 12๐
Rotor resistance starter needs slip rings
A rotor resistance starter is used only on slip ring (wound rotor) induction motors. Squirrel cage motors have no external rotor terminals for it. Recall: which motor type takes a rotor resistance starter? Answer: slip ring.
- Fact 11 of 12๐ฅ
Extra rotor resistance gives high starting torque
External resistance in the rotor circuit raises starting torque and lowers starting current. The resistance is cut out in steps as the motor speeds up. Recall: when is rotor resistance cut out? Answer: as speed rises.
- Fact 12 of 12๐๏ธ
Slip rings shorted at full speed
At full speed, the slip rings are shorted, so the motor runs like a normal induction motor. A crane hoist at a Kerala port needs this high starting torque. Recall: what is done to the slip rings at full speed? Answer: shorted.