    Governor sets how much kW each alternator takes

    The engine governor, like a throttle, sets the real power (kW) share of each alternator. Like a bus driver pressing the accelerator, more fuel means more load. Recall: which control sets kW? (Governor)

  2. Fact 2 of 12

    Equal droop shares load by kVA rating

    With equal governor droop, load splits in proportion to kVA rating. A 500 kVA set takes twice the load of a 250 kVA set. Recall: equal droop shares load by what? (Rating)

  3. Fact 3 of 12

    Frequency is common to all parallel alternators

    All alternators in parallel run at one common frequency. Adding governor input to one machine raises its kW, so system frequency rises slightly. Recall: is frequency common or separate? (Common)

  4. Fact 4 of 12

    Excitation controls reactive power (kVAR)

    Field current, or excitation, sets the reactive power (kVAR) of each alternator. More excitation means more kVAR and higher terminal voltage. Recall: excitation controls which power? (Reactive)

  5. Fact 5 of 12

    Over-excited alternator supplies lagging current

    Over-excitation makes the alternator supply reactive power with lagging power factor. Like a pump motor in a Kerala house, lagging loads need this kVAR support. Recall: over-excitation gives which power factor? (Lagging)

  6. Fact 6 of 12

    Under-excited alternator absorbs reactive power

    Under-excitation makes the alternator absorb reactive power, giving a leading power factor. It may lose synchronism and slip out of step. Recall: under-excited gives which power factor? (Leading)

  7. Fact 7 of 12

    Excitation changes kVAR, not the kW split

    Changing excitation mainly changes reactive power, not the kW sharing. The kW share depends on engine input. Recall: excitation mainly changes kW or kVAR? (kVAR)

  8. Fact 8 of 12

    Real and reactive power formulas for three-phase alternators

    Real power: P = sqrt(3) x V x I x cos(phi), in watts with line values. Reactive power: Q = sqrt(3) x V x I x sin(phi). Recall: which term gives kVAR? (sin phi)

  9. Fact 9 of 12

    Power factor is kW divided by kVA

    Power factor = kW / kVA = cos(phi). A lower power factor needs more current for the same kW, so cables and windings heat more. Recall: lower power factor means more what? (Current)

  10. Fact 10 of 12

    Unload a set before opening its breaker

    Reduce governor input so the set carries little kW before opening its breaker. This avoids a sudden load shock to the other sets. Recall: unload using which control? (Governor)

  11. Fact 11 of 12

    High excitation heats the field winding

    High excitation raises the field current, which heats the rotor winding. Excitation limits must be watched on every set. Recall: high excitation heats which winding? (Field or rotor)

  12. Fact 12 of 12

    Unequal excitation causes circulating reactive current

    Two parallel alternators with unequal excitation exchange reactive current, even with no outside load. Their terminal voltages differ, and this current flows between them. Recall: what current flows between them? (Reactive)