  1. Fact 1 of 12

    Power triangle: three sides

    Real power (kW) does useful work. Apparent power (kVA) is the total supplied, the hypotenuse. Formula: kVA^2 = kW^2 + kVAR^2. Recall: which side is the hypotenuse? Answer: kVA.

  2. Fact 2 of 12

    Power factor is cos phi

    Power factor = kW / kVA, which equals cos phi. It shows how much supplied power does useful work. Recall: power factor = kW divided by what? Answer: kVA.

  3. Fact 3 of 12

    Reactive power does no work

    Reactive power (kVAR) builds magnetic fields in motors and transformers but does no useful work. It swings between the source and the load. Recall: unit of reactive power? Answer: kVAR.

  4. Fact 4 of 12

    Inductive loads make current lag

    Motors, transformers and tube light chokes store energy in magnetic fields. So current lags voltage and power factor falls. Recall: which load type causes lagging current? Answer: inductive.

  5. Fact 5 of 12

    Lightly loaded motors have low pf

    An induction motor on light load still draws large magnetising current, so its power factor drops. Kerala example: a pump set running half-empty on a farm. Recall: when does motor power factor drop? Answer: light load.

  6. Fact 6 of 12

    Tube light chokes lower pf

    The choke in a fluorescent tube is an inductive coil, so an uncorrected tube has low power factor. Capacitors are fitted to correct it. Recall: which tube light part causes the lag? Answer: choke.

  7. Fact 7 of 12

    Low pf means higher current

    For the same kW, current I = kW / (V x pf), so lower pf means more current. Kerala example: a busy workshop needs thicker cable than a home with the same kW. Recall: at low pf, is current higher or lower? Answer: higher.

  8. Fact 8 of 12

    Copper loss depends on current squared

    Copper loss = I^2 x R in cables and transformer windings. Doubling the current makes the loss four times bigger, so wires heat up. Recall: copper loss formula? Answer: I^2 R.

  9. Fact 9 of 12

    Higher current gives bigger voltage drop

    More current through line resistance causes a bigger voltage drop along the feeder. Kerala example: bulbs dim at the far end of a long village line. Recall: which quantity increases along a long line? Answer: voltage drop.

  10. Fact 10 of 12

    Why it is called static

    A static capacitor has no rotating parts, unlike a synchronous condenser. It supplies leading kVAR that cancels the lagging kVAR, with little maintenance. Recall: why is it called static? Answer: no moving parts.

  11. Fact 11 of 12

    Capacitors connect in parallel

    Static capacitors are connected in parallel with the inductive load, often near the motor. They supply reactive power locally, so less comes from the line. Recall: how are pf capacitors connected? Answer: parallel.

  12. Fact 12 of 12

    Sizing the capacitor in kVAR

    Required kVAR = kW x (tan phi1 - tan phi2), where phi1 is the old angle and phi2 the target. Kerala example: sizing a bank for a rice mill motor. Recall: kVAR formula uses which function? Answer: tan phi.