Do you know?
[AE] Power system stability and load flow - part 2
- Fact 1 of 12⚡
Swing equation: the core formula
Formula: (2H/ωs) d²δ/dt² = Pm − Pe, with Pm mechanical input and Pe electrical output. Why: a mismatch speeds or slows the rotor, like a KSEB generator on sudden load. Recall: what is Pe? (Electrical output)
- Fact 2 of 12🔄
H is measured in seconds
H is the inertia constant, in MJ/MVA, which equals seconds. Why: higher H means the rotor resists speed change more, like a heavy flywheel. Recall: what unit is H in? (MJ/MVA, or seconds)
- Fact 3 of 12🛵
Accelerating power: Pa = Pm − Pe
Pa = Pm − Pe is the accelerating power. Why: positive Pa speeds the rotor, like a scooter engine pulling harder than the road load. Recall: what is Pa when Pm equals Pe? (Zero)
- Fact 4 of 12⚖️
Equal area criterion: the key rule
Stability needs A1 (accelerating area) equal to A2 (decelerating area) on the power-angle curve. Why: energy gained speeding up must be lost slowing down, like a bus braking over a speed bump. Recall: A1 must equal what? (A2)
- Fact 5 of 12⏱️
Critical clearing angle
Critical clearing angle is the largest rotor angle at which a fault can be cleared safely. Why: faster breakers raise it, like a pressure cooker vent released early. Recall: a faster breaker does what to it? (Raises it)
- Fact 6 of 12🧭
Equal area works for one machine only
Equal area criterion applies to a single machine on an infinite bus, so it is graphical and simple. Why: real grids with many machines need numerical tools instead. Recall: which bus model does it use? (Infinite bus)
- Fact 7 of 12🔁
Gauss-Seidel uses latest values at once
Each bus voltage updates immediately using the newest values of the other buses. Why: each step is cheap, but convergence is slow. Recall: which values does Gauss-Seidel use at once? (Latest updated)
- Fact 8 of 12🚀
Acceleration factor of about 1.6
A factor of about 1.6 is typically applied to Gauss-Seidel voltage corrections to speed convergence. Why: it pushes each correction further, saving iterations. Recall: typical Gauss-Seidel factor? (1.6)
- Fact 9 of 12🧮
Gauss-Seidel avoids the Jacobian
Gauss-Seidel needs no Jacobian matrix, so each step is cheap and easy to code. Why: that cheapness is paid back with many more iterations on large grids. Recall: which matrix does it avoid? (Jacobian)
- Fact 10 of 12📐
Newton-Raphson: quadratic convergence
Newton-Raphson load flow converges quadratically, so the error roughly squares each iteration. Why: it needs only a few iterations, even on big networks. Recall: what kind of convergence is it? (Quadratic)
- Fact 11 of 12🧠
Newton-Raphson update formula
Update: x(k+1) = x(k) − J^-1 f(x(k)), where J is the Jacobian and f holds power mismatches. Why: each step solves one linear system, which is heavier work per iteration. Recall: what does f(x) hold? (Power mismatches)
- Fact 12 of 12🏭
Why utilities pick Newton-Raphson
Newton-Raphson is preferred for large power networks because it needs fewer iterations overall. Why: heavier steps are worth it when the grid has many buses, like a substation control room. Recall: is NR cheaper per iteration? (No)