[BOTH] Circuit breakers and relays - part 3
- Fact 1 of 12๐งโ๐ฌ
Buchholz relay: who invented it and when?
Max Buchholz, a German engineer, invented it in 1921. Exam tip: learn the name and year together. Recall: Who invented the Buchholz relay?
- Fact 2 of 12๐ข๏ธ
Where the Buchholz relay sits
It sits in the pipe joining the transformer tank to the conservator. Gas from an internal fault collects in it. Kerala example: a KSEB substation transformer. Recall: Where is the Buchholz relay fitted?
- Fact 3 of 12๐ซง
Buchholz relay: two stages
The alarm stage catches slow gas build-up. The trip stage acts on a sudden rush of oil. Why: the operator gets time to check before a shutdown. Recall: Which stage trips the breaker?
- Fact 4 of 12โก
Only oil-filled transformers
The Buchholz relay is used only on oil-filled transformers with a conservator. Dry-type transformers have no oil to make gas. Recall: Which transformer type skips the Buchholz relay?
- Fact 5 of 12โ๏ธ
Differential relay: in equals out
It compares current entering and leaving a protected zone. In a healthy zone the two are equal. A difference means a fault inside. Recall: What two currents does it compare?
- Fact 6 of 12๐ฒ
Differential relay protects only its zone
It protects the zone between its two sets of CTs, used for transformers, generators and busbars. A fault outside the zone does not trip it. Recall: Does a differential relay trip for outside faults?
- Fact 7 of 12๐
Percentage differential: the bias
Its trip setting rises with the through current. This stops false tripping when CTs mismatch during a heavy external fault. Kerala example: protection of a large KSEB transformer. Recall: What does the bias prevent?
- Fact 8 of 12๐
Second harmonic restraint
When a transformer is switched on, inrush current looks like a fault. Its second harmonic content blocks the differential trip. Recall: Which harmonic restrains the trip?
- Fact 9 of 12๐
Distance relay: Z = V / I
It measures impedance, Z = V divided by I. Line impedance grows with distance, so Z shows how far the fault is. Kerala example: a fault on a KSEB 110 kV line. Recall: What is Z equal to?
- Fact 10 of 12๐ฏ
Distance relay Zone 1 reach
Zone 1 is set to cover about 80 to 85 percent of the line. It trips instantly. Why: CT and VT errors must not make it overreach into the next line. Recall: What percent of the line does Zone 1 cover?
- Fact 11 of 12๐ก๏ธ
Zone 2 and Zone 3 backup
Zone 2 and Zone 3 act as backup for neighbouring lines, with time delays. Zone 2 reaches beyond Zone 1, and Zone 3 reaches further still. Recall: Which zone trips instantly?
- Fact 12 of 12โญ
Mho characteristic: a circle
Many distance relays use a mho characteristic, which is a circle on the R-X diagram passing through the origin. Why: it responds well to fault direction and reach. Recall: What shape is a mho characteristic?